Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/17/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) THERE IS NO ACCESS TO BACK YARD-RECALL |
|
| 12/15/2004 | ELECTRIC - FINAL | Cancelled | IVRS - Ri canceled | |
| 12/13/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection :The bonding is not per code.| THE GROUND RODS MUST BE LOCATED NEAR THE SERVICE ENTRANCE EQUIPMENT THE GROUNDING CONDUCTOR MUST BE NEW. USE OF AN OLD UFER WIRE IS NOT PERMITTED. IT IS UNPROVEN AND ITS CONDITION FOR ITS ENTIRE LENGTH IS UNKNOWN THE CIRCUIT BREAKER POSITIONS ABOVE 6 FEET 7" FROM NATURAL GRADE MUST BE BLOCKED FROM FUTURE USE THE POOL EQUIPMENT AND THE DRYER REQUIRE A GROUND WIRE NOT JUST A NEUTRAL CORRECT AND RECALL |
|
| 12/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1) ALL NEW SERVICES (UPGRADED, REPLACEMENT ETC.) REQUIRE A NEW GROUNDING SYSTEM. THE EXISTING SYSTEM (UFER) IS CONSIDERED "UN-PROVEN" |