Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :*OK TO RECONNECT | |
| 12/01/2004 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*/ 1) A GROUND BAR IS NEEDED AT SUB-PANEL 2) FILL UNUSED OPENINGS IN BACK OF PANEL WITH EXPOSED COMBUSTIBLE MATERIAL 3) NM CABLE NEED PHYSICAL PROTECTION 4) BOXES AND DEVICES TO BE WEATHER PROOF 5) PLEASE LABEL ALL BREAKERS BOTH PANELS 6) WORK TO BE PEFORMED BY LICENSED ELECTRICAL CONTRACTOR THIS IS A RENTAL UNIT |