Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :*OK TO CLEAR | |
| 01/25/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* CORRECTIONS REQUIRED, 1) THE TOTAL CONNECTED LOAD TO SUB PANELS ETC, EQUAL THREE HUNDRED & TEN AMPS ( 310 A ) PLEASE SUBMIT LOAD CALCULATIONS FOR MAIN PANEL & SUB PANELS. 2) THE SUB PANEL & OTHER EQUIPMENT LOADS REQUIRE A GROUND WIRE BE INCLUDED. THE PVC CONDUIT DOES NOT PROVIDE A GROUND PATH. 3) THE CONDUCTORS TO SUB PANEL ARE TOLL LARGE FOR THE CIRCUIT BREAKER TERMINALS, TRIMMING STANDS FROM CONDUCTOR IS NOT PERMITTED. 4) THE GROUND WIRE MUST BE RUN UNSPLICED. 5) PROVIDE COPY OF VALID BUILDING PERMIT FOR THE NEWLY CONSTRUCTED PORCH. PROVIDE NEW FLOOR PLAN FOR STRUCTURES ON PROPERTY. THANKS. |