Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2004 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection :*/ 1) NEED RISER 2) SEPERATE GROUND AND NEUTRAL AT SUB PANEL AND INSTALL GROUND BAR 3) TIGHTEN LOOSE CONNECTORS 4) REVERSE GROUND ROD CLAMPS 5) STRAP GROUND TO BLDG 6) NEED PERMANENT METAL ADDRESS LABEL 7) LABEL BREAKERS 8) SUB-PANELS TO HAVE 4 CONDUCTOR WIRE |