Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR #2 CEC MH | |
| 03/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 01/19/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVETED TO COVER. 2) INSTALL 2 GOUND RODS 6' MIN APART. 3) SUPPORT PVC CONDUIT & #4 BARE TO WALL. 4) CONDUIT TO SHALLOW, MUST BE 18" DEEP MIN. |