Permit: T04EL02322

Parcel: 124172240

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/15/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR #2 CEC MH
03/14/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
01/19/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVETED TO COVER. 2) INSTALL 2 GOUND RODS 6' MIN APART. 3) SUPPORT PVC CONDUIT & #4 BARE TO WALL. 4) CONDUIT TO SHALLOW, MUST BE 18" DEEP MIN.