Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 12/08/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio/STILL CANNOT ACCESS CIRCUIT BREAKER PANEL AT SERVICE AREA DUE TO TREE. A RE-INSPECTION FEE IS ASSESED, PAY RE-FEE AT 201 N STONE PRIOR TO FUTURE INSPECTIONS. PLEASE READ NOTES LEFT BY INSPECTOR |
|
| 12/06/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NO COMPLIANCE WITH NOTE #3 LAST INSPECTION 2) YOU MUST HAVE AREA IN FRONT OF ELECTRICAL SERVICE EQUIPMENT CLEAR OF ANY OBSTRUCTIONS FOR A DISTANCE OF 36" IN FRONT AND THE WIDTH OF THE EQUIPMENT INCLUDING TREES/SHRUBS OR ANY OTHER OBSTRUCTION, PER 110-26 NEC |
|
| 11/22/2004 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*/1)WE HAVE GROUNDED RECEPTICALS ON AN UNGROUNDED SYSTEM 2)INSTALL SMOKE DETECTORS AS PER MANUFACTURES INSTRUCTIONS 3)MAINTAIN WORKING CLEARENCE IN FRONT OF ELECTRIC SERVICE 4)WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR |