Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/18/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)THE #4 BARE WIRE GOING TO GROUND RODS, THE WEST GROUND WIRE TIED INTO CLAMP CORRECTLY, THE EAST GROUND ROD CLAMP INCORRECT, THE #4 WIRE MUST GO THRU THE CLAMP ONT THE CURVED SIDE OF ACORN CLAMP NOT BOLT SIDE. 2)THE TWO NEUTRALS OF THE APARTMENT FEEDERS ARE TIED INTO THE GROUND BAR - THEY MUST BE TIED TO THE NEUTRAL BAR BELOW METER #1229, THE #4 WIRE FROM THE RODS MUST ALSO TIE HERE. THE GREEN GROUNDS TIE TO THE LUG FASTENED TO SIDE OF ENCLOSURE, ALSO THE #4 BOND WIRE TO WATER AND GAS BOND 3)INSTALL MISSING SCREW COVER ON TOP METER COVER |