Permit: T04EL02295

Parcel: 124061990


Addresses:

1227 E 10TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL02295

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/18/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)THE #4 BARE WIRE GOING TO GROUND RODS, THE WEST GROUND WIRE TIED INTO CLAMP CORRECTLY, THE EAST GROUND ROD CLAMP INCORRECT, THE #4 WIRE MUST GO THRU THE CLAMP ONT THE CURVED SIDE OF ACORN CLAMP NOT BOLT SIDE. 2)THE TWO NEUTRALS OF THE APARTMENT FEEDERS ARE TIED INTO THE GROUND BAR - THEY MUST BE TIED TO THE NEUTRAL BAR BELOW METER #1229, THE #4 WIRE FROM THE RODS MUST ALSO TIE HERE. THE GREEN GROUNDS TIE TO THE LUG FASTENED TO SIDE OF ENCLOSURE, ALSO THE #4 BOND WIRE TO WATER AND GAS BOND 3)INSTALL MISSING SCREW COVER ON TOP METER COVER