Permit: T04EL02290

Parcel: 116010840

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/05/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/29/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service entrance is not per code.| 215* 1. # 14 WIRE HAS BEEN PLACED UNDER 20AMP CIRCUIT BREAKERS. 2. INDEX IS INCOMPLETE. 3. MINIMUM SIZE MOUNTING HARDWARE FOR ELECTRICAL PANEL IS 1/4" LAG BOLT & LEAD SHIELD OR EQUIVALENT. 4. ADD A STRAP TO RISER PIPE-WITHIN 8" OF TOP OF PANEL. 5. THE FRIESE BOARD ( BIRD BOARD) IS NON STRUCTURAL AND IS NOT TO BE USED TO ATTACH STRAPS. CORRECT & RECALL.