Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL02277
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/FINISH GRD RODS SLEVES FOR SUB HEADS? 1)DENIED ELECTRICAL WORK UNDER SERVICE NOT FINISHED 2)CANNOT LOCATE 2ND GROUND ROD-DRIVE 1ST ONE DOWN TO GRADE. 3)GROUND WIRE #4 ONLY SUFFICENT FOR A 200A TOTAL SER. 4)PLEASE LIST LIC ELECT CONTRACTOR 5)STRAP GROUNDWIRE UNDER SERVICES |
|
12/07/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL A SECOND GROUND ROD SET AT 6' DISTANCE, MINIMUM, FROM THE FIRST ROD 2) FINISH THE BURIAL OF THE GROUND WIRE AND PLEASE WIRE BRUSH ALL PAINT OFF THE SURFACE OF PIPES WHERE GROUND CLAMP IS ATTACHED 3) PLACE SUPPORT STRAPS ON GROUND WIRE TO KEEP IT CLOSE TO THE BLDG WALL 4) COMPLETE THE CABLEING AND CONDUIT WORK FOR THE FEEDER WIRES TO THE INTERIOR OF EACH APARTMENT SUB PANEL 5) RECALL INSPECTION FOR WED 12/08/04 |
|
12/06/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |