Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/15/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CORRECT THE MC CABLE IN ROMEX BOXES BY REPLACING MC WITH ROMEX. 2) ADD ADDRESS TO PANEL. MUST BE METTALIC. 3) MARK PANEL SCHEDULE | |
| 11/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE HOUSE HAS NEW/RECENT ELECTRICAL WIRING AND THE SERVICE PANEL IS ALSO NEW. THE PANEL IS 125 AMP W/ 125 AMP MAIN CB. THE INCOMING SERVICE IS 60 AMP. THIS IS A MISMATCH. A NEW SERVICE AND SERVICE ENTRANCE IS NEEDED. PLEASE HAVE A NEW PERMIT ISSUED FOR A REWIRE AND SERVICE UPGRADE |