Permit: T04EL02251

Parcel: 10605121A


Addresses:

861 W THURBER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/18/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/17/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/15/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) CORRECT THE MC CABLE IN ROMEX BOXES BY REPLACING MC WITH ROMEX. 2) ADD ADDRESS TO PANEL. MUST BE METTALIC. 3) MARK PANEL SCHEDULE
11/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) THE HOUSE HAS NEW/RECENT ELECTRICAL WIRING AND THE SERVICE PANEL IS ALSO NEW. THE PANEL IS 125 AMP W/ 125 AMP MAIN CB. THE INCOMING SERVICE IS 60 AMP. THIS IS A MISMATCH. A NEW SERVICE AND SERVICE ENTRANCE IS NEEDED. PLEASE HAVE A NEW PERMIT ISSUED FOR A REWIRE AND SERVICE UPGRADE