Permit: T04EL02250

Parcel: 138200480

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*OK TO CLEAR RECON
11/12/2004 ELECTRIC - FINAL Denied SMOKE DETECTORS IN BEDROOMS NEED TO BE @ LEAST 3' FROM VENTS. SWITCH WIRING IN HALL TO BE FINISHED. CHANGED OUT RECEPS. ON KITCHEN COUNTER NEED GFI PROTECTION. NEW A/C & WATER HTR ADDED-PERMITS NEEDED FOR THESE. GOUND WIRE TO SERVICE HAS BEEN CUT. 3/4" EMT RUN TO SERVICE NOT SUPPORTED, ALSO NEED A CLOSED NIPPLE W/ 2 LOCKNUTS INTO CAN, NOT A CHASE NIPPLE. PERMANENTLY ADDRESS SERVCIE.