Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/08/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*OK TO CLEAR RECON |
| 11/12/2004 |
ELECTRIC - FINAL |
|
Denied |
SMOKE DETECTORS IN BEDROOMS NEED TO BE @ LEAST 3' FROM VENTS. SWITCH WIRING IN HALL TO BE FINISHED. CHANGED OUT RECEPS. ON KITCHEN COUNTER NEED GFI PROTECTION. NEW A/C & WATER HTR ADDED-PERMITS NEEDED FOR THESE. GOUND WIRE TO SERVICE HAS BEEN CUT. 3/4" EMT RUN TO SERVICE NOT SUPPORTED, ALSO NEED A CLOSED NIPPLE W/ 2 LOCKNUTS INTO CAN, NOT A CHASE NIPPLE. PERMANENTLY ADDRESS SERVCIE. |