Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TO CLOSE WALL 1) SWITCHES TO BE GROUNDED 380-9 2) NM CABLE TO BE SUPPORTED WITH 12" OF RECESSED CANS. 3) RECESSED CANS TO BE LOWERED TO 1/4" OR LESS FROM SURFACE 370-20. 4) PLEASE VERIFY DERATING VALUES FOR MULTIGA??DIMMERS. 5) M/C CABLE TO TERMINATE INTO A FITTING AND APPROVED BOX. ALSO SUPPORT WITHIN 12" OF BOX. 6) CORRECTLY IDENTIFY CONDUCTOR AS PER 200-7. 7) #8 NM CABLE TO BE SIZE FOR AMPACITY PER 336-26. 8) COMPLETE #4 OF PREVIOUS INSPECTION |
|
| 03/15/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE OPEN UP WALLS FOR ACCESS TO WIRING FOR INSPECTION. A? CEILING ACCESS IS OK FOR CEILING OR OPEN UP CEILING. 2) FINISH PREVIOUS ITEMS # 1, 3, 4, 5 |
|
| 03/02/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE VERIFY PERMITS FOR INTERIOR WORK AND PHOTO VOLTA?? SYSTEM. 2) MAINTAIN WORKING CLEARANCE IN FRONT OF ELECTRI SERVICES 3) ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL LUG. 4) SEAL ENTRANCES WITH AN APPROVED DEVICE ABOVE CURRENT CARR?? PARTS 5) TIGHTEN LOOSE FITTINGS |