Permit: T04EL02200

Parcel: 127033310


Addresses:

5525 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* OK TO CLOSE WALL 1) SWITCHES TO BE GROUNDED 380-9
2) NM CABLE TO BE SUPPORTED WITH 12" OF RECESSED CANS. 3) RECESSED CANS TO BE LOWERED TO 1/4" OR LESS FROM SURFACE 370-20. 4) PLEASE VERIFY DERATING VALUES FOR MULTIGA??DIMMERS. 5) M/C CABLE TO TERMINATE INTO A FITTING AND APPROVED BOX. ALSO SUPPORT WITHIN 12" OF BOX. 6) CORRECTLY IDENTIFY CONDUCTOR AS PER 200-7. 7) #8 NM CABLE TO BE SIZE FOR AMPACITY PER 336-26. 8) COMPLETE #4 OF PREVIOUS INSPECTION
03/15/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) PLEASE OPEN UP WALLS FOR ACCESS TO WIRING FOR INSPECTION. A? CEILING ACCESS IS OK FOR CEILING OR OPEN UP CEILING. 2) FINISH PREVIOUS ITEMS # 1, 3, 4, 5
03/02/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) PLEASE VERIFY PERMITS FOR INTERIOR WORK AND PHOTO VOLTA?? SYSTEM. 2) MAINTAIN WORKING CLEARANCE IN FRONT OF ELECTRI SERVICES 3) ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL LUG. 4) SEAL ENTRANCES WITH AN APPROVED DEVICE ABOVE CURRENT CARR?? PARTS 5) TIGHTEN LOOSE FITTINGS