Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR | |
| 11/05/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) IDENTIFICATION OF 617 AND 615 APPEARS TO BE REVERSED 2) LOOSE FITTING 3) NEED TO SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 4) HAVE LICENSED CONTRACTOR RE-CHECK ALL OF INSTALLATION |
|
| 11/01/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 2) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS REQUIREMENTS 3) TIGHTEN LOOSE WIRE TERMINATIONS 4) SUPPORT CONDUITS ABOVE PANEL |