Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL02175
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE USE OF CIRCUIT BREAKERS OTHER THAN THOSE MANUFACTURED BY MURRAY ELECTRIC PRODUCTS (THE INSTALLED PANEL IS PROHIBITED) CHANGE OUT TO MURRAY C.B.'S 2) CHECK YOUR LIGHTING AND GENERAL LOAD CIRCUITS FOR WIRE SIZE. YOU HAVE USED ALL 20 AMP CB'S FOR ALL CIRCUITS-THESE MAY BE OVERSIZED FOR SOME CIRCUITS IN A HOUSE BUILT IN THE EARLY 1950'S |