Permit: T04EL02167

Parcel: 117041540


Addresses:

147 W 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR
02/01/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* FINAL PENDING INSTALLATION OF BOLT DOWN KIT FOR BACKFED CIRCUIT BREAKER AT SUB-PANEL
10/27/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*/THE WATER PIPE AND GAS PIPE BONDING CLAMPS MUST BE RELOCATED TO THE HOUSE SIDE (WHERE PIPE ENTERS HOUSE OR CLOSEST POINT) OF THE PIPES. NOTICE: BE ADVISED, THIS PERMIT IS FOR A SERVICE UPGRDE ONLY. IT DOES NOT GRANT YOU AUTHORITY TO INSTALL SUB PANELS OR REWIRE HOUSES. SECURE A PERMIT FOR ANY OTHER WORK OF IMPROVEMENT