Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04EL02165
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO CLEAR CD/TS | |
11/04/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The grounding electrode conductor is not installed per code.| 220*/ 1) STRAP/SUPPORT NEEDED FOR RISER PIPE AT APT. 5 2) THE WATER HEATERS ARE NEXT TO EACH OTHER SUCH THAT THE GROUNDS MUST BE CONNECTED. RUN YOUR GROUNDING CONDUCTOR FROM SERVICE 1 TO COLD WTR. PIPE, TO HOT WTR. PIPE, TO GAS PIPE TO COLD WTR. PIPE, TO HOT WTR PIPE, TO GAS PIPE TO SERVICE #2 SO TAHT ALL OF THE METAL (PIPES, WATER HEATERS, AND PANEL BOXES) SYSTEMS ARE COMMON AND CREATE A COMMON GROUND PLANE |