Permit: T04EL02165

Parcel: 123020080


Addresses:

3002 E GRANT RD #05

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/08/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :* OK TO CLEAR CD/TS
11/04/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The grounding electrode conductor is not installed per code.| 220*/ 1) STRAP/SUPPORT NEEDED FOR RISER PIPE AT APT. 5
2) THE WATER HEATERS ARE NEXT TO EACH OTHER SUCH THAT THE GROUNDS MUST BE CONNECTED. RUN YOUR GROUNDING CONDUCTOR FROM SERVICE 1 TO COLD WTR. PIPE, TO HOT WTR. PIPE, TO GAS PIPE TO COLD WTR. PIPE, TO HOT WTR PIPE, TO GAS PIPE TO SERVICE #2 SO TAHT ALL OF THE METAL (PIPES, WATER HEATERS, AND PANEL BOXES) SYSTEMS ARE COMMON AND CREATE A COMMON GROUND PLANE