Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04EL02159
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/04/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/02/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE WIRED INCORRECTLY 2) RISER TO SMALL 3) WIRING INSIDE RISER 100A MAIN BREAKER 200A GROUNDING REQUIRED 2 GRD RODS, WATER AND GAS BOND 4) ADDRESS SERVICE 5) HOLES TO BE SEALED 6) BUS ON THIS SERVICE WEATHERED 7) CONDUITS AT BOTTOM TO BE SECURED 8) RISER TO BE 2" IMC OR ? 9) MUST USE MEYERS HUB AT ENTRY 10) SUGGEST SERVICE BE UPGRADED. TO 100 AMPS |
|
| 10/29/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/26/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |