Permit: T04EL02159

Parcel: 120071160


Addresses:

7 W LINCOLN ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T04EL02159

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
11/04/2004 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
11/02/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/29/2004 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
10/26/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CONDUIT TO BE AS PER T&P STANDARDS 2)USE APPROVED STRAPING METHODS 3)SERVICE HAS BEEN PAINTED ON ALL INTERIOR BUSSING AND TERMANATIONS - THIS IS AN UNSAFE SERVICE 4)FILL UNUSED OPENINGS IN DISCONNECT 5)MISSING DEAD FRONT 6)OBTAIN SERVICES OF A LICENSED ELECTRICAL CONTRACTOR