Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/04/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode connection. New services require all new grounding circuit. Existing ground to wtr. pipe is not acceptable as it is an unproven ground. You may bond gas line to cold wtr. pipe at wtr. heater |
|