Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/20/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/1)EXPOSED ROMEX WIRING FOR 240VOUT OUTLET FOR DRYER NOT ALLOWED 2)INSTALL SMOKE DETECTORS IN BEDROOMS 3)EXPOSED WIRING AROUND OUTSIDE WALLS, OPEN J-BOXES, ALSO NOT RATED FOR OUTDOOR USE 4)THIS IS A DUPLEX WITH MULTIPLE CODE VIOLATIONS AROUND BOTH UNITS. PREVIOUS INSPECTION FOR UNIT NEXT DOOR 2432 HAS VIOLATIONS & EXPIRED PERMITS ON RECORD. OBTAIN RECORDS AT 201 N. STONE TO MAKE REPAIRS TO SATISFY VIOLATIONS & EXPIRED PERMITS, ALL WORK TO BE DONE BY C-11 LICENSED CONTR. 5)NO CLEARANCE FOR POWER TO EITHER UNIT ON THIS PREMESES TILL WIRING UP TO CODE AND VIOLATIONS SATISFIED |