Permit: T04EL02122

Parcel: 130102110


Addresses:

3109 E 28TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/29/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK TO CLEAR RECON. PLAESE INSTALL SMOKE DETECTORS IN BEDROOMS, RE-CALL INSP FOR FINAL APPROVAL WHEN DONE
10/25/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/LICENSED C-11 CONTRACTOR TO PROPERLY ELIMINATE HAZARDOUS UNUSED WIRING AND TO MAKE NECESSARY REPAIRS. EG. ROMEX UNDERGROUND, EXPOSED S.E. CABLE, CAR FLEX LONGER THAN 6' AND IN PROPER TERMINATION, MISSING COVER PLATER. WATCH GROUNDING RECEPTACLE IN UNGROUNDED SYSTEM