Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 10/27/2004 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*/1)SUPPORT RISER & CONDUIT WITHIN 3' BELOW ROOF 2)USE APPROVED FITTING WITH LLD CHASE NIPPLE NOT APPROVED 3)ONLY ONE NEUTRAL CONDUCTOR PER TERMANRE? LUG 4)A 2ND GROUND ROF IS NEEDED, GAS & WATER BOND ARE NEEDED 5)INDENIFY NEUTRAL CONDUCTOR BY LUG AND CLOSE TO WEATHER HEAD 6)STRAP GROUNDING ELECTRODE CONDUCTOR TO STRUCTOR 7)BREAKER TO BE LISTED BY MANUFACTORES 8)WIRE NUTS TO BE LISTED |