Inspection History: ELECTRIC - FINAL
Permit Number - T04EL02092
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/28/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) YOU WERE ASKED TO VERIFY CIRCLED ITEM ABOVE 2) J-BOX BELOW EAVE SHOULD BE WEATHER PROOF |
|
10/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service entrance is not per code.| 215*/NEED: 1)PROOF RISER CONDUCTORS ARE "SUNLIGHT RESISTANT". 2) PANEL INDEX 3)ALL CIRCUIT BREAKERS TO INTERIOR ARE 20AMP. THESE HOUSES WERE NOT WIRED, ORIGINALLY, FOR ALL 20AMP. CIRCUITS. PLEASE CHECK THE INTERIOR WIRING FOR AW GAUGE SIZE & CIRCUIT BREAKER ACCORDINGLY. THANKS |