Permit: T04EL02092

Parcel: 124081880


Addresses:

1427 E 10TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL02092

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/28/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) YOU WERE ASKED TO VERIFY CIRCLED ITEM ABOVE 2) J-BOX BELOW EAVE SHOULD BE WEATHER PROOF
10/15/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The service entrance is not per code.| 215*/NEED: 1)PROOF RISER CONDUCTORS ARE "SUNLIGHT RESISTANT". 2) PANEL INDEX 3)ALL CIRCUIT BREAKERS TO INTERIOR ARE 20AMP. THESE HOUSES WERE NOT WIRED, ORIGINALLY, FOR ALL 20AMP. CIRCUITS. PLEASE CHECK THE INTERIOR WIRING FOR AW GAUGE SIZE & CIRCUIT BREAKER ACCORDINGLY. THANKS