Permit: T04EL02060


Addresses:

5740 E GLENN ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T04EL02060

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
10/12/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*/NOTHING DONE STUIE? COST WRITE UP
10/11/2004 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*/1)A BOND BUSHING IS NEEDED FOR RISER 250.92 2)PLEASE UNCOVER 1ST GROUND ROD FOR INSPECTION 3)GROUNDING ELECTRODE CONDUCTOR TO TERMANATE AT GROUNDED TERMANAL 4)RECABLE BREAKERS. THIS IS A SALES TRAILER