Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/11/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)SERVICE CONDUCTORS RUN INTO 3M RATHER THAN 2M 2)SCHEDULE 40 PVC CANNOT BE RUN ABOVE GROUND ON SURFACE MUST BE BURRIED AT LEAST 18" OR 24" IF TRAFFIC CAN GO OVER IT. |