Permit: T04EL02007

Parcel: 10318011B

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T04EL02007

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
10/07/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :The wiring is not complete or does not comply with code.| NEED PERMANENT METAL OR PLASTIC ENGRAVED ADDRESS TAG SCREWED OR RIVETED INTO METER BASE
USE 1/4" HARDWARE FOR RISER IE: LAG SCREWS
NEED 2 GROUND RODS 5/8" x 8' DRIVEN INTO GROUND 6' APART MINIMUM USE #4 BORE COPPER MINIMUM
NEED A WATER BOND AND GAS BOND
WILL NEED AN APPROVED JUNCTION BOX IN LIEU OF OLD PANEL BOARD
MUST USE CUTLERHAMMER BREAKER