Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T04EL01994
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/04/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : 1) WE HAVE EXPOSED CONDUCTORS IN WALL - CONDUIT SYSTEM TO BE MECHAN?/ CONTINOUS. 2) WHERE IS BREAKER TIE HANDLE FROM MANUFACTURER? |
|
| 09/30/2004 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*NOT READY. 1) FINISH #4, 5, AND 6 OF PREVIOUS INSPECTION. 2) HAVE CONTRACTOR LEAVE A LETTER ON COMPANY LETTERHEAD ACCEPTING RESPONSIBILITY FOR WORK DONE. | |
| 09/28/2004 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*/1)BATH ROOM RECEPTICLE TO BE GFI PROTECTED 2)WE HAVE GROUNDED RECEPTICALS ON AN UNGROUNDED SYSTEM 3)INSTALL RECEPTICALS INTO WALL 4)DRYER INSTALLATON DOES NOT MEET CODES. 5)OUTSIDE BOXS & CONDUIT REATTACH TO WALL 6)PROTECT CONDUCTOR/CABLE ENTERING MAIN DISCONNECT 7)DO NOT DOUBLE ON NEUTRALS OR GROUNDS AT SUB PANEL. WORK TO BE PERFORMED BY LICENSED ELECTRICAL CONTRACTOR. PLEASE VERIFY AFTER COMPLETION |