Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/08/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| RECEPTACLES IN FRONT PORCH MUST BE GFI TYPE WITH APPROVED WEATHERPROOF COVER EXPOSED WIRING IN WATER HEATER RM NOT ALLOWED ROMEX WIRE BELOW 8' MUST BE PHYSICALLY PROTECTED INSTALL SMOKE DETECTORS IN BEDROOMS, REPAIR LIGHT FIXTURES, CEILING FANS NO COMPLIANCE WITH NOTES FROM LAST INSPECTION - A RE-FEE WILL BE ASSESED AT NEXT INSP IF NO COMPLIANCE |
|
| 10/03/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 09/30/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| REPAIR COVER TO SERVICE PANEL, ALSO FILL IN BLANK SPACES ON DEADFRONT ELECTRICAL WIRING IN BACK STOREROOM NOT PER CODE. PROVIDE DOCUMENTATION FOR CARPORT & STOREROOM REFLECTING PERMITS OBTAINED FOR CONSTRUCTION & APPROVALS FOR INSPECTIONS ALL WIRING OUTSIDE UNITS NOT APPROVED FOR OUTDOOR USE RE-CALL INSP WHEN ACCESS AVAILABLE INSIDE UNIT ALL WORK TO BE DONE BY C-11 LICENSED CONTRACTOR |