Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/09/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK TO CLEAR INC |
| 02/01/2005 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection :NOTES: 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED ORRIVITED TO COVER NO MARKING PEN. 2) 2 GROUND RODS REQUIRED 6' MIN APART. BOND WATER & GAS PIPING. 3) NEW SERVICE UPGRADED TO 200 AMP. 4) DO NOT SPLICE GROUND WIRE FROM GROUND RODS. 5) OUTSIDE J-BOXES NEED TO BE WEATHER PROOF. |