Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL01981

Parcel: 116170320

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/01/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/28/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) WILL NEED A SECOND GROUND ROD (MINIMUM 6' APART) 2) WILL NEED A GAS BOND 3) WILL NEED A WATER BOND 4) WILL NEED A PERMANENT ADDRESS TAG WITH ADDRESS EXACTLY AS PERMIT SHOWS