Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2004 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection :* |
| 10/26/2004 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection :*/1)NEW SERVICES REQUIRE COMPLETE NEW GROUND. YOUR GROUNDING IS INCOMPLETE BECAUSE THE WATER PIPE MUST ALSO BE GROUNDED WITH THE NEW GROUND WIRE LOOP 2)A NEW CIRCUIT DIRECTORY MUST BE PLACED OR WRITTEN ON THE PANEL COVER OR NEXT TO EACH CIRCUIT BREAKER TO I.D. EACH AREA SERVED. 3)WHERE IS YOUR "INSPECTION CARD" (YELLOW TAN)? LEAVE IN PANEL. RECALL |
| 10/21/2004 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection :* |
| 09/30/2004 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection :* |