Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01947
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) ACORN CLAMP LISTED FOR ONLY ONE CONDUCTOR-DBL BACK IS TWO CONDUCTORS 2) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE 3) PLEASE VERIFY PERMIT FOR INSTALLATION OF SPA | |
09/24/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/1)CHANGE ADDRESS TAG TO REFLECT EAST LINDEN, NOT NORTH. 2)PLEASE AFFORD PHYSICAL PROTECTION OF U.F. WIRE DOWN TO BELOW GRADE. 3)INSTALL GROUND WIRE IN CAPTIVE SIDE OF ROD CLAMP (INTO WEDGE) 4)STRAP GROUND WIRE FIRMLY TO WALL AT EAST SIDE. |