Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/29/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* OK TO CLEAR INC ECO. CALL FOR FINAL AFTER TIE-IN | |
| 09/27/2004 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/23/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES. 1) CANNOT BEND GROUND ROD, NEC REQUIRES 8' IN EARTH & TOP OF ROD TO BE FLUSH WITH FINISHED GRADE, ART 250. DO NOT CUT OFF. 2) ? CIRCUIT BREAKERS. WILL NEED TO SEE WIRING METHODS FOR BRANCH CIRCUITS. 3) BOND WATER & GAS PIPING. 4) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO COVER. 5) #6 DECK SCREWS NOT APPROVED FOR RISER SUPPORT, USE MIN 1/4" BOLTS. 6) LOCATION OF SERVICE OVER FLOWER BED WITH 2 ' WALLS IN VIOLATION OF 110-26 NEC FOR WORKING CLEARANCE, ALSO DISTANCE FROM GROUND LEVEL TO OVER CURRENT DEVICE CANNOT EXCEED 6' 7" PER NEC. |