Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL01891

Parcel: 107111910

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/21/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/17/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
1) THE SERVICE IS REQUIRED TO HAVE A PERMANENT ADDRESS LABEL ( NO MARKER OR PEN) 2) SEAL HOLE BOTTOM OF MAIN DISCONNECT. 3) REMOVE 30 AMP FUSES AND INSTALL 15 AMP FUSES ON #14 WIRE CIRCUITS AND 20 AMP FUSES ON # 12 WIRE INSIDE OK. NOTE: TO OWNER ALL 3 METERS SHOULD BE ADDRESSED AND ALL HOLES SEALED.