Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/02/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) GATE LOCKED, NO ACCESS | |
| 09/21/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS. 1) PVC LB NOT GLUED TO CONDUIT | |
| 09/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) RISER TO BE SUPPORTED BY AT LEAST 1/4" HARDWARE 2) NEED AT LEAST 2/0 COPPER FOR CONDUCTORS IN RISER TO GO UP TO 200 AMP SERVICE 3) NO PERMIT FOR A/C UNIT 4) ALL CIRCUIT BREAKERS IN PANEL TO BE MURRAY MP OR MH TYPE SEE LABEL IN PANEL 5) SERVICE UPGRADES REQUIRE UPGRADED PANEL SCHEDULES 6) WRONG TYPE OF CLAMP ON GA LINE 7) ROOF USE A REDWOOD BLOCK OR UNISTRUT TO SUPPOR CONDUIT 8) DISCONNECT FOR A/C IMPROPERLY SUPPORTED |