Permit: T04EL01864

Parcel: 12218234A

Inspection Status: Denied

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
09/13/2004 FIRE - FINAL Denied 1. Provide verification that fire sprinkler system is designed for shelf storage to 19 feet storage height.
2. Plans/permits required for shelving exceeding 8 feet in height.
3. Fire sprinklers required under open grated walkways.
4. Fire sprinkler required for 2nd floor corridor.
5. Fire sprinkler modifications required plans/permits by licensed fire sprinkler contractor.
09/13/2004 FIRE - FINAL Approved Fire approval for electric reconnect only. Fire sprinkler work must be completed prior to allowing occupancy.