Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2004 | FIRE - FINAL | Denied | 1. Provide verification that fire sprinkler system is designed for shelf storage to 19 feet storage height. 2. Plans/permits required for shelving exceeding 8 feet in height. 3. Fire sprinklers required under open grated walkways. 4. Fire sprinkler required for 2nd floor corridor. 5. Fire sprinkler modifications required plans/permits by licensed fire sprinkler contractor. |
|
| 09/13/2004 | FIRE - FINAL | Approved | Fire approval for electric reconnect only. Fire sprinkler work must be completed prior to allowing occupancy. |