Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/16/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The bonding is not per code.| 235*/PLEASE CORRECT: 1)#14 AWG RATED 15 AMPS HAS BEEN TERMINATED ON 20 AMP CIRCUIT BREAKERS. CHANGE CB'S TO ISA 2)FILL OUT CIRCUIT DIRECTORE 3)RUN #6 BARE GROUND WIRE FROM PANEL NEUTRAL BAR TO EACH OF THE OTHER DISCONNECTS. THE METAL OF ALL CANS MUST BE BONDED TO THE GROUNDING BAR. RECALL WHEN READY |