09/15/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/09/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :VERIFY WATER AND GAS BOND
TAPE NEUTRAL OUT OF WEATHERHEAD WHITE
CHANGE GREEN TAPE TO WHITE INSIDE METER SECTION
A RISER ABOVE 3' OFF ROOF NEEDS A KICKER SUPPORT OR GUY BACK SUPPORT