Permit: T04EL01810

Parcel: 122170740

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/17/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/1)WHERE IS WATER BOND AS PER #2 PREVIOUS INSPECTION FOR OTHER UNITS 2) BOND JUNCTION BOXES 250-148 3)SEPERATE GRADS? & NEUTRACS? SFTER OVER CORRENT DEVICE
09/03/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/THE GAS PIPES OF EACH UNIT MUST BE BONDED TO THE GROUNDING WIRE. THIS IS DONE TO SUPPLY GROUND TO THE PIPE AND ANY APPLIANCE CONNECTED TO IT
2)IT APPEARS THAT EACH UNIT MAY HAVE ITS OWN WATER SUPPLY. IF THIS IS THE CASE THEN EACH WATER PIPE/LINE ENTERING THE UNIT (3) MUST BE BONDED TO THE SERVICE GROUND.
CALL FOR FINAL WHEN CUT OVER IS COMPLETE
THIS APPLIES TO UNITS 4, 5 & 6 AS WELL