Permit: T04EL01801

Parcel: 11706075A


Addresses:

415 E 9TH ST #01


Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T04EL01801

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
09/13/2004 ELECTRIC - SERVICE UPGRADE Partial Approval 1. OK TO CLEAR SERVICE INCREASE CALL BACK FOR FINAL WHEN CHANGE OVER COMPLETE. 2. DRIVE GROUND RODS TO GRADE TO AVOID TRIOP HAZARD. 3. 30 AMP BREAKERS NEED A HANDLE TIE LIKE 100AMP BREAKER HAS.
09/02/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :The service is not per code.| BE ADVISED, YOUR INSTALLATION DOES NOT
1. MEET THE MINIMUM PIPE SIZE REQUIREMENT SET BY TEP FOR RISERS HIGHER THAN 3 FEET ABOVE ROOF
2. A 2ND GROUND ROD, SET 6' AWAY FROM THE OTHER ONE IS REQUIRED
3. THE 3/4" EMT CONDUIT IS INCORRECTLY TERMINATED TO THE JUNCTION BOX
4. A PERMANENT ADDRESS MUST BE PUT ON THE METER PANEL DO NOT USE PENCIL, PEN, MAGIC MARKER ETC. USE METAL STRIP OT INDIVIDUAL NUMBERS
5. MARK THE NEW CIRCUIT BREAKER POSITIONS WITH NAME OF AREA SERVED - KITCHEN, BEDRROM ETC
6. THE MOUNTING SCREWS MUST BE A MINIMUM OF 1/4" IN SIZE. SHEET METAL SCREWS ARE NOT ALLOWED