Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T04EL01801
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1. OK TO CLEAR SERVICE INCREASE CALL BACK FOR FINAL WHEN CHANGE OVER COMPLETE. 2. DRIVE GROUND RODS TO GRADE TO AVOID TRIOP HAZARD. 3. 30 AMP BREAKERS NEED A HANDLE TIE LIKE 100AMP BREAKER HAS. | |
09/02/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection :The service is not per code.| BE ADVISED, YOUR INSTALLATION DOES NOT 1. MEET THE MINIMUM PIPE SIZE REQUIREMENT SET BY TEP FOR RISERS HIGHER THAN 3 FEET ABOVE ROOF 2. A 2ND GROUND ROD, SET 6' AWAY FROM THE OTHER ONE IS REQUIRED 3. THE 3/4" EMT CONDUIT IS INCORRECTLY TERMINATED TO THE JUNCTION BOX 4. A PERMANENT ADDRESS MUST BE PUT ON THE METER PANEL DO NOT USE PENCIL, PEN, MAGIC MARKER ETC. USE METAL STRIP OT INDIVIDUAL NUMBERS 5. MARK THE NEW CIRCUIT BREAKER POSITIONS WITH NAME OF AREA SERVED - KITCHEN, BEDRROM ETC 6. THE MOUNTING SCREWS MUST BE A MINIMUM OF 1/4" IN SIZE. SHEET METAL SCREWS ARE NOT ALLOWED |