Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2012 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 02/27/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METER TO BE WIRED TO METER ALL IN ONE 2) BRANCH CIRCUITS IN RACEWAY OVER FILLED, DETERIORATING TO BE CHECKED 3) GET ELECTRICIAN TO DO WORK BEFORE CALLING FOR RE-INSPECTION |
|
| 09/15/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*/ 1) POWER CLEARANCE HOLD. REMODEL/NEW WIRING AT INTERIOR WILL NEED ACCURATE CITY APPROVED PLANS ON ALL WORK, IE. ELECTRICAL, MECHANICAL, ETC... DO NOT COVER ANY WORK | |
| 08/31/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) METAL ADDRESS REQUIRED ON SERVICE 2) USE ONLY LISTED BREAKERS 3) GROUND RODS TO BE 6' APART-DRIVE TO GRADE 4) CANNOT USE METER COMPARTMENT FOR LOAD CIRCUITS 5) 3/4" EMT ENTRANCE ON SOUTH SIDE HAS TO BEHIND DEAD FRONT COVER 6) KICKER SUPPORT ON ROOF TO BE IN OPPOSITE SIDE FROM PULL 7) PANEL SCHEDULE REQUIRED ON SERVICE 8) SUPPORT GROUND WIRE TO WALL 9) GAS BOND AND WATER BOND TO BE VERIFIED |