Permit: T04EL01785

Parcel: 134211330


Addresses:

7054 E TIMROD ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/01/2012 ELECTRIC - SERVICE UPGRADE Approved
02/27/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) METER TO BE WIRED TO METER ALL IN ONE
2) BRANCH CIRCUITS IN RACEWAY OVER FILLED, DETERIORATING TO BE CHECKED
3) GET ELECTRICIAN TO DO WORK BEFORE CALLING FOR RE-INSPECTION
09/15/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*/ 1) POWER CLEARANCE HOLD. REMODEL/NEW WIRING AT INTERIOR WILL NEED ACCURATE CITY APPROVED PLANS ON ALL WORK, IE. ELECTRICAL, MECHANICAL, ETC... DO NOT COVER ANY WORK
08/31/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) METAL ADDRESS REQUIRED ON SERVICE 2) USE ONLY LISTED BREAKERS 3) GROUND RODS TO BE 6' APART-DRIVE TO GRADE 4) CANNOT USE METER COMPARTMENT FOR LOAD CIRCUITS 5) 3/4" EMT ENTRANCE ON SOUTH SIDE HAS TO BEHIND DEAD FRONT COVER 6) KICKER SUPPORT ON ROOF TO BE IN OPPOSITE SIDE FROM PULL 7) PANEL SCHEDULE REQUIRED ON SERVICE 8) SUPPORT GROUND WIRE TO WALL 9) GAS BOND AND WATER BOND TO BE VERIFIED