Permit: T04EL01767

Parcel: 125071440


Addresses:

2636 E 5TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/29/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/31/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*/DENIED-CORRECTIONS REQUIRED,
1)INSTALL PERMANENT ADDRESS ON METER SIDE. EMBOSSED METAL STRIP IS PREFFERED. DO NOT USE PENCIK, PEN, CRAYON, MAGIC MARKER, ETC./
2)EXPOSE THE ENDS OF THE GROUND RODS DOWN TO THE CLAMP FOR INSPECTION.
3)MOVE COLD WATER PIPE GROUND TO THE INCOMING PIPE (HOUSE SIDE OF VALUE). THE HOSE BIBB YOU ATTACHED TO IS NOT CONNECTED TO WTR-IT IS NOT ACTIVE
4)THE GAS PIPING BOND MUST BE MOVED TO THE "HOUSE SIDE" PIPING. CLEAN ALL PIPING WITH WIRE BRUSH BEFORE APPLYING CLAMP/
5)THE PANEL DIRECTORY SHOULD BE MORE SPECIFIC. INDICATE NORTH-SOUTH-ETC. FOR OUTLETS-OR-KITCHE, BEDRMS-ETS.(GEN. NOT ACCEPTABLE)
6)THE "GEN. OUTLETS OUTSIDE"-SHOULD THESE BE CFI CIRCUIT BREAKERS?
7)ADD CLAMP TO RISEN CONDUIT -WITHIN 8" OF PANEL TOP
8)MINIMUM EQUIP MOUNTING HARDWARE IS 1/4 LAG-OR SHEILD