Permit: T04EL01766

Parcel: 133040490


Addresses:

9225 E HELEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/08/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/02/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :WE HAVE CONDUCTOR OVERFIL IN 3/4" CONDUIT
STRAP GROUNDING ELECTRODE CONDUCTOR TO BUILDING
A BONDING DEVICE IS NEEDED ON BOTH SIDES OF SECURE NIPPLE
GROUNDING EQUIPMENT CONDUCTORS (ALUM) NEED ANTI-OXIDE COMPOUND