Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/02/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :WE HAVE CONDUCTOR OVERFIL IN 3/4" CONDUIT STRAP GROUNDING ELECTRODE CONDUCTOR TO BUILDING A BONDING DEVICE IS NEEDED ON BOTH SIDES OF SECURE NIPPLE GROUNDING EQUIPMENT CONDUCTORS (ALUM) NEED ANTI-OXIDE COMPOUND |