Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01757
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR CALLED TEP 1) BOND BUSHINGS ON SERVICE NIPPLE ARE NEEDED. 2) SEALING DEVICE IS NEEDED AT TOP OF PANEL. 3) PLEASE BOND GAS. 4) GROUNDING CONDUCTORS TOB AS PER MANUFACTURERS RECOMMENDATIONS |