Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR. NOTE THAT METER BASE IS MISSING LUG . TEP TOLD CUSTOMER THAT THEY WOULD TAKE CARE OF THAT. | |
| 09/09/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SERVICE DISCONNECT HAS WATER DAMAGE INSIDE, NEEDS TO BE REPLACED WITH RAIN TITE 2) CONTR. TO BRING WIRING ON ROOF UP TO CODE AS NECESSARY 3) CHANGE CONTR. NAME ON PERMIT |
|
| 09/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| POST ADDRESS PLEASE SERVICE OUTDATED , IN NEED OF UPGRADE MELTED FUSE ON MAIN DISCONNECT INDICATES THAT SERVICE WAS OVERLOADED WHEN IN USE EXPOSED WIRING UNDER CANOPY AT LIGHT FIXTURES CASHER BOTH LOCKED AT CANOPY PLUG UNUSED OPENINGS IN J-BOXES AND CONDUIT PULL FITTINGS THROUGH-OUT IF SERVICE IS TO BE UPGRADED AT 400AMPS OR MORE PROVIDE APPROVED PLANS OR ALSO IF NEW WIRING TO BE INSTALLED |