Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/05/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) PEDESTALS | |
| 09/10/2004 | ELECTRIC - FINAL | Not ready for Inspection | NOT READY | |
| 08/25/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*/ 1) THE TOTAL COMBINED/MARKED AMPERAGE HEAD ON THE SOURCE LOAD CENTER PANEL FAR EXCEEDS IT'S RATING. SUBMIT LOAD CALC'S OR-RUN NEW LOADS TO PARK MAIN PANEL 2) UNABLE TO READ SIZE OF COPPER FEEDER WIRE 3) COPPER TO PLENIUM SPLICE MUS TBE BY WAY OF TWO COMPARTMENT LUG OR TERMINAL |