Permit: T04EL01744

Parcel: 124080370


Addresses:

1521 E 8TH ST

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/08/2004 ELECTRIC - FINAL Denied IVRS - Inspection :The service entrance is not per code.| NEED PERMANENT ENGRAVED METAL OR PLASTIC ADDRESS TAG SCREWED INTO METER BASE
LISTING AND CODE DOES NOT ALLOW TO EXIT LOAD WIRES THROUGH TOP OF END WALL
ROD, HORIZONTAL TO BE 2.5 FT DEEP, OTHER ROD NOT TO EXCEED 45 DEG ANGLE
PLEASE RECHECK ALL - THIS IS NOT A COMPLETE ITEMIZATION