Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| PLEASE SUBMIT FLOOR PLAN WITH ELECTRICLLAYOUT TO COT DSD FOR REVIEW AND PERMITS THIS HOUSE HAS BEEN REWIRED AND HAS SOME FEATURES AND ADDITIONS WHICH WERE CONSTRUCTED WITHOUT PERMIT |
|
| 08/31/2004 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/30/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* |
|
| 08/27/2004 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/26/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210*/ 1) ALL CIRCUIT BREAKERS ARE 20 AMP-WAS THE HOUSE REWIRED ? NORMALLY LIGHTING AND POWER TO BEDROOMS IS 15 AMP 2) THE PANEL AND MAIN BREAKER ARE MANUFACTURED BY SIEMENS/ITE, BUT THE BRANCH CIRCUIT BREAKERS ARE CROUSE HINDS AND MURRAY. UNLESS ALLOWED BY SPECIAL PERMISSION FROM THE PANEL MANUFACTURER OTHER CIRCUIT BREAKERS ARE NOT ALLOWED IN TO BE USED IN ANOTHER MANUFACTURERS PANEL 3) GROUND ROD CLAMPS OF THE TWO PIECE CLAMP TYPE, MUST HAVE BRASS OR STAINLESS SCREWS/BOLTS 4) CLAMP GROUND WIRES SECURELY TO WALL 5) THE HOUSE APPEARS TO HAVE BEEN REMODELED AND ADDED TO, YET OUR RECORDS DO NOT SHOW ANY PERMITS FOR THE WORK OF IMPROVEMENT. PLEASE EXPLAIN 6) MARK THE NEUTRAL CONDUCTOR WITH WHITE TAPE AT THE WEATHERHEAD 7) A PERMANENT-METAL-ADDRESS MUST BE ATTACHED TO THE PANEL ON THE METER SIDE. DO NOT USE PEN, PENCIL OR MAGIC MARKER |