Permit: T04EL01693

Parcel: 123151430

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T04EL01693

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
08/19/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The service entrance is not per code.| 215*/DENIED-GROUNDING IS INCOMPLETE.
NEC ARTICLE 250 REQUIRES ALL METAL PIPINGT ON THE PREMISES BE GROUNDED.
ADD THE GAS PIPES, WHEN THEY ENTER THE BUILDING, AND THE COLD WATER PIPE (EITHER AT THE WATER HEATER OR PRIMMARY POINT OF ENTRY), AND A BONDING JUMPER FROM COLD TO HOT WATER PIPES AT THE WTR HEATER (TO DEFEAT THE DIELECTRIC UNIONS).
COMPLETE & RECALL. LEAVE NOTE WITH DIRECTIONS WHERE WTR HTR IS LOCATED.