Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 08/19/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The service entrance is not per code.| 215*/DENIED-GROUNDING IS INCOMPLETE. NEC ARTICLE 250 REQUIRES ALL METAL PIPINGT ON THE PREMISES BE GROUNDED. ADD THE GAS PIPES, WHEN THEY ENTER THE BUILDING, AND THE COLD WATER PIPE (EITHER AT THE WATER HEATER OR PRIMMARY POINT OF ENTRY), AND A BONDING JUMPER FROM COLD TO HOT WATER PIPES AT THE WTR HEATER (TO DEFEAT THE DIELECTRIC UNIONS). COMPLETE & RECALL. LEAVE NOTE WITH DIRECTIONS WHERE WTR HTR IS LOCATED. |