Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01676
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR. RECALL FINAL. SUBA PANEL WILL NEED TO BE ISOLATED, ALL HO?"PLUGGED UP" AND PERMANENTLY IDENTIFY EACH UNIT SUB PANEL. PLEASE CLEAR TEMP POWER ( PER DIANE HERRON CLEARANCE ON HOLD UNTIL ALL UNITS ARE CLEARED) |
|
09/07/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*/ 1) THE GAS METER-PIPES INTO BLDG MUST BE STRAPPED/GRD BONDED SO EACH METER IS BONDED TO SERVICE 2) THE RISER CONDUIT/LB NIPPLE INTO BOX REQUIRES A BOND BUSHING AND GROUND TO BOX 3) EXPOSE THE GROUND RODS DOWN TO THE CLAMP FOR INSPECTION. WHERE IS WATER PIPE BOND ? 4) GROUNDING INCOMPLETE |